CT Chamber specification
The figures for the standard pre-wired CT Chamber, and what each one means for the metering point.
| Chamber | |
|---|---|
| Current rating | 400 A (loads up to 280 kVA) |
| Height | To follow |
| Width | To follow |
| Depth | To follow |
| Weight | To follow |
| Material | To follow |
| Current transformers | |
| Ratio | 400/5 (standard) |
| Accuracy class | 0.5S |
| Rating | 5 VA |
| Certification | CT accuracy certificates, printed and as PDF |
| Orientation | Fitted to your power flow direction |
What each figure means
400 A
The current the chamber is rated to carry, suitable for loads up to 280 kVA.
400/5
The CT ratio. The CTs reduce the current reaching the meter by a factor of 80, so the meter never sees more than 5 A. It is programmed to scale the reading back up.
5 VA
The CT rating, or burden: the load each CT can drive while staying within its accuracy class. The meter and the wiring to it must stay within this.
Class 0.5S
The accuracy class. The CTs stay within 0.5% at their rated current, and the S means the accuracy is specified down to low loads as well, so light-load periods are still measured properly.